Zhurnal Tekhnicheskoi Fiziki, 2024, Volume 94, Issue 11, Pages 1909–1914 DOI: https://doi.org/10.61011/JTF.2024.11.59108.98-24
(Mi jtf6906)
|
|
|
|
Electrophysics
Simulator of operation of relay protection devices of high-voltage network under the influence of geoinduced currents
A. A. Tren'kina, A. B. Buyanova, E. P. Grabchakb, S. V. Voevodina, A. V. Limonova a Federal State Unitary Enterprise "Russian Federal Nuclear Center — All-Russian Research Institute of Experimental Physics", Sarov, Nizhny Novgorod region
b Joint Institute for High Temperatures, Russian Academy of Sciences, Moscow
DOI:
https://doi.org/10.61011/JTF.2024.11.59108.98-24
Abstract:
A mobile simulator for experimental simulation of operation of relay protection devices in the high-voltage and ultrahigh voltage network under the influence of geoinduced currents was developed. The simulator at the initial digital signature allows providing currents at the inputs of relay protection devices in the frequency range from 0 up to 50 kHz; the currents simulate signals from measuring current transformers. The simulator is developed on an easily accessible element base. The equipment weight is 20 kg, the power supply is 220 V/50 Hz, and the power consumption is not more than 1.6 kW. The initial signals for the simulator can be the currents recorded at the active power objects, and also obtained as a result of calculation simulation of the energy system operation or defined as standards.
Keywords:
relay protection of high-voltage network, simulation of influence, geoinduced current.
Received: 23.03.2024 Revised: 31.07.2024 Accepted: 08.07.2024
Citation:
A. A. Tren'kin, A. B. Buyanov, E. P. Grabchak, S. V. Voevodin, A. V. Limonov, “Simulator of operation of relay protection devices of high-voltage network under the influence of geoinduced currents”, Zhurnal Tekhnicheskoi Fiziki, 94:11 (2024), 1909–1914
Linking options:
https://www.mathnet.ru/eng/jtf6906 https://www.mathnet.ru/eng/jtf/v94/i11/p1909
|
| Statistics & downloads: |
| Abstract page: | 56 | | Full-text PDF : | 40 |
|